Mfg Part Number: GJ4-Z4-1 | Alternate P/N: GJ4Z41 |
Manufacturer: Eaton Corp | NSN : 5925-01-222-4379 |
NIIN : 012224379 | Item Name : circuit breaker |
CAGE Code : 74193 | FSC : 5925 Circuit Breakers |
Thank you for your interest in our available GJ4-Z4-1 NSN part. This part number GJ4-Z4-1 is a Circuit Breaker listed under the FSC 5925 Circuit Breakers, and it is manufactured by Eaton Corp. At Internet of Components, all of our stock and inventory are available for purchase today, ready to ship with short lead times and competitive pricing. Whether you are in need of parts that are new, used, or obsolete, our team of industry experts is readily available 24/7x365 to fulfill all of your operational
“*” Symbols for mandatory fields
Internet of Components is a premier supplier of GJ4-Z4-1 NSN component, and we carry recently requested NSN components such as 5925012224379. We strive to only provide our customers with quality parts, which is why we choose to source our inventory from thousands of global manufacturers such as Eaton Corp. If you are interested in this particular item, we invite you to begin the purchasing process for GJ4-Z4-1 today by filling out and submitting an Instant RFQ. Once received, a member of our staff will review and reach out to you in 15 minutes or less to provide a personalized quote that caters towards your individual needs. Get started on the purchasing process today and see how we are revolutionizing the purchasing process.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-222-4379 Item Description: Circuit Breaker | 5925 | 012224379 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
GJ4-Z4-1 | 5 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 7.120 INCHES NOMINAL |
ADAT | BODY WIDTH | 6.000 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 5.940 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 3.828 INCHES NOMINAL |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.500 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.220 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 4.300 INCHES NOMINAL |
AKPX | POLE QUANTITY | 4 |
APNQ | ARC QUENCHING METHOD | DEION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 130.0 AMPERES DC FOURTH LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 45.0 AMPERES AC FIRST LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 45.0 AMPERES AC SECOND LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 45.0 AMPERES AC THIRD LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 130.0 DC FOURTH LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC FIRST LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC THIRD LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 DC FOURTH LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC FIRST LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC SECOND LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 18000.0 AC THIRD LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 2 CONTROL |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | RELAY TRIP FOURTH LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SECOND LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP THIRD LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.190 INCHES |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT EACH POLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.250 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT FIRST LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.250 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT SECOND LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.250 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT THIRD LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.900 MINIMUM AT 200 PCT AND 1.300 MAXIMUM AT 200 PCT FOURTH LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 10.0 DC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 30.0 DC |
FEAT | SPECIAL FEATURES | RELAY COIL RATED AT 24.0 VDC,16.0 OHMS |
FREQ | FREQUENCY IN HERTZ | 400.0 FIRST LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 SECOND LOCATION |
FREQ | FREQUENCY IN HERTZ | 400.0 THIRD LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 8 THREADED STUD |
Don’t forget That If You’d Ever Like a Quote for Parts Within 15 Minutes or Less, You Can Fill out the Instant RFQ form On this Website’S Homepage.
Request for Quote